Delta MH300 Series Drive Parameters

Delta MH300 Series Drive Parameters – here you can find all parameter for programming. With the help of these parameter you can easily program drive. All list of parameter like actual signal, motor data, limit parameter and fault function.

For complete parameter list Download Manual

Factory Reset
02–009
Start/Stop
00–210digital keypad
1External terminals
2RS-485 communication
3CANopen communication
2-wire/3-wire
02–001Start forward/Start Reverse
22-wire
33-wire
Stop Mode
00–220Ramp
1Coast
Speed Reference
00–200Digital Keypad
1RS-485 communication
2Analog Input
3external UP / DOWN terminals
6CANopen communication
Motor Pot
02–0319MI3 Frequency up command
02–0420MI4 Frequency down command
Jog Function
02–076MI7 – JOG operation
01–22……HZJOG frequency
Acc/Dec Time
01–12……sAcceleration time
01–13……sDeceleration time
Relay Output
02–131Indication during RUN
9Drive is ready
11Malfunction indication
Motor Data
05–01……AMotor Current
05–02……KWMotor Power
05–03……rpmMotor Speed
Modbus Comm
09–00……Station ID/Comm Address
Baud Rate
09–010Baud rate 4800 bps
1Baud rate 9600 bps
2Baud rate 19200 bps
3Baud rate 38400 bps
Parity
09–0407, N, 2 for ASCII
17, E, 1 for ASCII
27, O, 1 for ASCII
38, N, 2 for RTU
48, E, 1 for RTU
58, O, 1 for RTU
68, N, 1 for RTU
78, E, 2 for RTU
88, O, 2 for RTU
97, N, 1 for ASCII
107, E, 2 for ASCII
117, O, 2 for ASCII
Comm Fault
09–020Warning
3No action