F172 fault in WEG CFW900 Drive

F172 fault in WEG CFW900 Drive indicates a Power Heatsink Fan Speed Fault. This means one of the main cooling fans has failed or jammed, triggering a trip to prevent overheating.
Cause:

Heat sink fan 2 speed fault.

  • Dirt on the fan blades and rolling bearings.
  • Defective fan.
  • Defective fan power supply connection.

Remedy:

Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.