F30005 fault in Siemens V70 Drive

F30005 fault in Siemens V70 Drive indicates Power unit Overload I2t. This means the inverter has been pushed past its continuous thermal current rating for too long, requiring a reduction in load to prevent hardware damage.
Cause:

The power unit was overloaded.

  • The permissible rated power unit current was exceeded for an inadmissibly long time.
  • The permissible load duty cycle was not maintained.

Remedy:

  • Reduce the continuous load.
  • Adapt the load duty cycle.
  • Check the motor and power unit rated currents.