Hitachi HH200 Drive – Find comprehensive resources for Hitachi HH200 AC drives, including product catalogs, manuals, price list, programming guides, fault, alarm, warnings & software support. Get expert assistance for troubleshooting and optimization.

Hitachi HH200 series is a line of low-voltage AC drives designed for a variety of industrial applications. These drives are used to control the speed of asynchronous motors, providing precise control and energy efficiency.
Features
Hitachi HH200 drive based on DSP control system, apply SVPWM control and a variety of protections for asynchronous motor drive. The air duct, hardware and software have been greatly improved for better environment adaptability and operation.
- More accurate motor auto tuning
- Multiple braking modes and instant stopping
- Perfect voltage and current control, reduce the fault protection time
- Separate air-duct Multiple installation modes,
- Wall mounting and flange mounting
- C3 input filter (standard configuration) and C2 filter (optional)
- Parallel installation
- Smaller installation space with low cost and beautiful appearance.
- Greener proper grounding
- Stronger corrosion-resistance excellent EMC performance
- Smaller size
- Various external interfaces and swappable terminal board convenient for replacement and maintenance
- High performance keypad
- Standard LED keypad
- Embedded braking units of 1.5-30 kW drive
- Supporting common DC bus
- Available on DC power supply
- Advanced Thermal Technology makes exact Thermal Design
- Wide Voltage Range meets the requirement of Grid Environment
Specifications
Function | Specification | |
Input | Input Voltage (V) | AC 3 ph 380 V (-15%)~440 V (+10%) |
Input Frequency (Hz) | 50 Hz or 60 Hz Allowed range. 47~63 Hz | |
Output | Output Voltage (V) | 0~input voltage |
Output Frequency (Hz) | 0~400 Hz | |
Technical Control Feature | Control Mode | SVPWM |
Motor Type | Asynchronous motor | |
Speed-adjusting Ratio | Asynchronous motor 1:100 | |
Starting Torque | Asynchronous motor: 0.5 Hz / 150% | |
Overload Capability | Heavy Duty: 150% of rated current 60 seconds Normal Duty: 120% of rated current 60 seconds | |
Running Control Feature | Frequency Setting | Digital setting, analog setting, pulse frequency setting, multi-step speed running setting, simple PLC setting, PID setting, MODBUS communication setting. Realize the shifting between the set combination and set channel. |
Auto Voltage Adjustment | Keep a stable voltage automatically when the grid voltage fluctuates | |
Fault Protection | Provide over 30 fault protection functions: overcurrent, overvoltage, undervoltage, overheating, phase failure and overload, etc. | |
Speed Tracking | Restart the rotating motor smoothly | |
Peripheral Interface | Terminal Analog Input Resolution | |
Terminal Switch Input Resolution | ||
Analog Input | 2 channels (Al1, Al2) 0~10 V / 0-20 mA and 1 channel (Al3) -10~10 V | |
Analog Output | 2 channels (A01, A02) 0~10 V / 0~20 mA | |
Digital Input | 8 channels common input, the Max. frequency: 1 kHz 1 channel high speed pulse input, the Max. frequency: 50 kHz | |
Digital Output | 1 channel high speed pulse output, the Max. frequency: 50 kHz; 1 channel Y terminal open collector output | |
Relay Output | 2 channels programmable relay output RO1A NO, RO1B NC, RO1C common terminal RO2A NO, RO2B NC, RO2C common terminal Contactor capability: 3A / AC 250 V,1A / DC 30 V | |
Others | Mountable Method | Wall, flange and floor mountable |
Temperature of the Running Environment | -10~50°C, derate above 40°C | |
Ingress Protection | IP20 | |
Cooling | Air-cooling | |
Braking Unit | Built-in braking unit up to HH200-300A / 370AP-4 External braking unit require for others | |
Braking Resistor | Optional external configuration | |
EMC Filter | Built-in C3 filter: meet the degree requirement of IEC61800-3 C3 External filter: meet the degree requirement of IEC61800-3 C2 |
Power ratings
Type Code | Power Rating P (KW) | I continuous (A) | ||
Heavy Duty (OL- 150% for 1 Min.) | Normal Duty (OL- 120% for 1 Min.) | Heavy Duty (OL- 150% for 1 Min.) | Normal Duty (OL- 120% for 1 Min.) | |
HH200-0R7A-4 | 0.7 | NA | 2.5 | NA |
HH200-1R5A-4 | 1.5 | NA | 3.7 | NA |
HH200-2R2A-4 | 2.2 | NA | 5 | NA |
HH200-4R0A/5R5AP-4 | 4 | 5.5 | 9.5 | 14 |
HH200-5R5A/7R5AP-4 | 5.5 | 7.5 | 14 | 18.5 |
HH200-7R5A/110AP-4 | 7.5 | 11 | 18.5 | 25 |
HH200-110A/150AP-4 | 11 | 15 | 25 | 32 |
HH200-150A/185AP-4 | 15 | 18.5 | 32 | 38 |
HH200-185A/220AP-4 | 18.5 | 22 | 38 | 45 |
HH200-220A/300AP-4 | 22 | 30 | 45 | 60 |
HH200-300A/370AP-4 | 30 | 37 | 60 | 75 |
HH200-370A/450AP-4 | 37 | 45 | 75 | 92 |
HH200-450A/550AP-4 | 45 | 55 | 92 | 115 |
HH200-550A/750AP-4 | 55 | 75 | 115 | 150 |
Applications
- Air Compressors
- Plastic Machinery
- Petroleum
- Mining
- HVAC and Water Supply
- Fan and Water Pumps and many more.