LFF1 fault in Schneider ATV12 Drive indicates an AI current lost fault. This means the 4-20mA signal on Analog Input 1 dropped below 2mA, pointing to a broken wire or failed sensor.
Cause: Detection if AI1 is current, scaling > 3 mA, and input < 2 mA.
Remedy:
- Check the terminal connection.