LS-Electric iG5A Drive – Find comprehensive resources for LS-Electric iG5A AC drives, including product catalogs, manuals, price list, programming guides, fault, alarm, warnings & software support. Get expert assistance for troubleshooting and optimization.
![LS-Electric iG5A Drive image](https://click2electro.com/wp-content/uploads/2025/01/LS-Electric-iG5A-Drive-image-1024x625.png)
The LS-Electric iG5A Drive is a general-purpose variable frequency drive (VFD) designed for a wide range of industrial applications. The iG5A series is a popular choice for general industrial applications due to its versatility, ease of use, and cost-effectiveness.
Features
- Sensorless Vector Control : The built-in sensorless vector control provides superb speed control and powerful torque.
- Built-in PID Control : The built-in PID function enables control of flow-rate, oil-pressure, temperature, etc without any extra controllers.
- Built-in Dynamic Braking Circuit : The built-in dynamic braking circuit minimizes deceleration time via braking resistors.
- Easy Change of Fan : iG5A is designed to easily change the fan in case of a fan breakdown.
- Cooling Fan Control : By controlling the cooling fan, iG5A provides a virtually quiet environment according to the status of operation.
- User-Friendly Interface : The 4-direction key provides easy handling and monitoring.
- Compact Size : The compact size is cost-efficient and allows for various applications. Same height from 0.4 to 4.0kW (128mm)
- Global Standard : iG5A series complies with CE and UL standards.
- PNP/NPN Input : Both PNP and NPN inputs become possible and these enable the user to use the outer power. To do so, users will be given a wide range of choices for selecting the controller.
Specification
1-phase 200V Class
SV ㅁㅁㅁ iG5A-1ㅁㅁ | 004 | 008 | 015 | |
---|---|---|---|---|
Max. Capacity 1) | [HP] | 0.5 | 1 | 2 |
[kW] | 0.4 | 0.75 | 1.5 | |
Output Rating | Capacity [kVA] 2) | 0.95 | 1.9 | 3.0 |
FLA [A] 3) | 2.5 | 5 | 8 | |
Max Frequency | 400 [Hz] 4) | |||
Max Voltage | 3 Phase 200 ~ 230V 5) | |||
Input Rating | Rated Voltage | 1phase 200~230 VAC (+10%, -15%) | ||
Rated Frequency | 50 ~ 60 [Hz] (±5%) | |||
Cooling Method | Forced Air Cooling | |||
Weight [kg] | 0.76 | 1.12 | 1.84 |
3-phase 200V Class
SV ㅁㅁㅁ iG5A-2ㅁㅁ | 004 | 008 | 015 | 022 | 037 | 040 | 055 | 075 | 110 | 150 | 185 | 220 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Max. Capacity 1) | [HP] | 0.5 | 1 | 2 | 3 | 5 | 5.4 | 7.5 | 10 | 15 | 20 | 25 | 30 |
[kW] | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 4.0 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |
Output Rating | Capacity [kVA] 2) | 0.95 | 1.9 | 3.0 | 4.5 | 6.1 | 6.5 | 9.1 | 12.2 | 17.5 | 22.9 | 28.2 | 33.5 |
FLA[A] 3) | 2.5 | 5 | 8 | 12 | 16 | 17 | 24 | 32 | 46 | 60 | 74 | 88 | |
Max Frequency | 400 [Hz] 4) | ||||||||||||
Max Voltage | 3 Phase 200 ~ 230V 5) | ||||||||||||
Input Rating | Rated Voltage | 3 phase 200~230 (+10%, -15%) | |||||||||||
Rated Frequency | 50~60 [Hz] (±5%) | ||||||||||||
Cooling Method | N/C 6) | Forced Air Cooling | |||||||||||
Weight [kg] | 0.76 | 0.77 | 1.12 | 1.84 | 1.89 | 1.89 | 3.66 | 3.66 | 9.0 | 9.0 | 13.3 | 13.3 |
3-phsae 400V Class
SV ㅁㅁㅁ iG5A-4ㅁㅁ | 004 | 008 | 015 | 022 | 037 | 040 | 055 | 075 | 110 | 150 | 185 | 220 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Max. Capacity 1) | [HP] | 0.5 | 1 | 2 | 3 | 5 | 5.4 | 7.5 | 10 | 15 | 20 | 25 | 30 |
[kW] | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 4.0 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |
Output Rating | Capacity [kVA] 2) | 0.95 | 1.9 | 3.0 | 4.5 | 6.1 | 6.9 | 9.1 | 12.2 | 18.3 | 22.9 | 29.7 | 34.3 |
FLA [A] 3) | 1.25 | 2.5 | 4 | 6 | 8 | 9 | 12 | 16 | 24 | 30 | 39 | 45 | |
Max Frequency | 400 [Hz] 4) | ||||||||||||
Voltage [V] | 3 Phase 380 ~ 480V 5) | ||||||||||||
Input Rating | Rated Voltage | 3 phase 380~480 VAC (+10%, -15%) | |||||||||||
Rated Frequency | 50~60 [Hz] (±5%) | ||||||||||||
Cooling Method | N/C 6) | Forced Air Cooling | |||||||||||
Weight [kg] | 0.76 | 0.77 | 1.12 | 1.84 | 1.89 | 1.89 | 3.66 | 3.66 | 9.0 | 9.0 | 13.3 | 13.3 |
1) Indicates the maximum applicable motor capacity when using the standard 4-pole LS motor.
2) Rated capacity is based on 220V for 200V series and 440V for 400V series.
3) Refer to 15-3 of the user manual when carrier frequency setting (39) is above 3kHz.
4) Max. frequency setting range is extended to 300Hz when H40 (Control mode select) is set to 3 (Sensorless vector control).
5) Max. output voltage cannot be higher than the input voltage. It can be programmable below the input voltage.
6) Self-Cooling