LS-Electric iP5A Drive – Find comprehensive resources for LS-Electric iP5A AC drives, including product catalogs, manuals, price list, programming guides, fault, alarm, warnings & software support. Get expert assistance for troubleshooting and optimization.
![LS-Electric iP5A Drive image](https://click2electro.com/wp-content/uploads/2025/01/LS-Electric-iP5A-Drive-image.png)
LS Starvert SV-iP5A has been specifically designed and created to provide competitive solutions for fan and pump applications. The iP5A, specifically designed for HVAC application, provides stable and cost-effective system performance.
Features
- Dual PID :When additional PID control or cascade PID control is required, dual PID provide users with various uses of the system with only iP5A.
- Multi Motor Control : The built-in algebra control function enables an inverter to control motors without a controller so that user can take advantage of energy-saving and lower costs.
- Sleep and Wake-Up : The built-in energy saving function makes the inverter stop automatically when the capacity is too low.
- Pre-Heater : The built-in pre-heater function prevents motor damage and inverter break-down caused from humidity.
- Flying Start : When the inverter drives many ventilators or when the fan in a big load system turns due to a natural displacement, iP5A operates the motor by automatically searching for the motor speed.
- Auto energy saving :iP5A provides the auto energy saving function by an optimal flux control which minimizes energy loss caused by load change.
- Improved Management from Instant Power-off and Power Dip Generation : During the power dip or instant power-off, which is generated by lightening, ground fault, and power-failure, loads still keep the mechanical energy and this energy flows back to inverter by regeneration. The power-failure guarantee time is extended by using this electrical character of the inverter.
- Constant and Stable Performance (24 hours 365 days) : Regardless of outside alteration such as input voltage variation by load change or weather effect, iP5A can handle motor and load with best performance.
- Safety Stop : When unexpected power-failure blocks the power supply, the inverter stops the motor by using energy of the load that prevents reoccurrence of accidents (Parameter setting is required).
Specification
Below table show LS-Electric iP5A Drive specifications:
3-phase 200V Class (0.75~30kW)
Model Number (SVㅁㅁㅁiP5A-2) | 008 | 015 | 022 | 037 | 055 | 075 | 110 | 150 | 185 | 220 | 300 | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 1.9 | 3.0 | 4.6 | 6.1 | 6.1 | 12.2 | 17.5 | 22.9 | 28.2 | 33.5 | 43.8 | |||
Output ratings | Fan or pump load | Motor rating 2) | (HP) | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 |
(kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | |||
Current [A] | 5 | 8 | 12 | 16 | 24 | 32 | 46 | 60 | 74 | 88 | 115 | |||
(110% over current) | 110% 1 Minute (Normal Duty) | |||||||||||||
General load | Motor rating | (HP) | 0.5 | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | |
(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |||
Current [A] | 2.5 | 5 | 8 | 12 | 17 | 23 | 33 | 44 | 54 | 68 | 84 | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | |||||||||||||
Frequency | 0.01~120 Hz | |||||||||||||
Voltage | 200~230V 3) | |||||||||||||
Input ratings | Voltage | 3Ø200~230V (-15%~+10%) | ||||||||||||
Frequency | 50/60 Hz (± 5%) | |||||||||||||
Protection degree | IP20 / UL Type1 | IP00 / UL Open 4) | ||||||||||||
Weight [kg (lbs.)] | 4.1 (9.0) | 4.2 (9.3) | 4.2 (9.3) | 4.9 (10.8) | 4.9 (10.8) | 6 (13.2) | 6 (13.2) | 13 (28.7) | 13.5 (29.8) | 20 (44.1) | 20 (44,1) |
3-phase 400V Class (0.75~90kW)
Model Number (SVㅁㅁㅁiP5A-4) | 008 | 015 | 022 | 037 | 055 | 075 | 110 | 150 | 185 | 220 | 300 | 370 | 450 | 550 | 750 | 900 | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 2.0 | 3.2 | 4.8 | 6.4 | 9.6 | 12.7 | 19.1 | 23.9 | 31.1 | 35.9 | 48.6 | 59.8 | 72.5 | 87.6 | 121.1 | 145.8 | |||
Output ratings | Fan or pump load | Motor rating 2) | (HP) | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 |
(kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | |||
Current [A] | 2.5 | 4 | 6 | 8 | 12 | 16 | 24 | 30 | 39 | 45 | 61 | 75 | 91 | 110 | 152 | 183 | |||
(110% over current) | 110% 1 Minute (Normal Duty) | ||||||||||||||||||
General load | Motor rating | (HP) | 0.5 | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | |
(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | |||
Current [A] | 1.25 | 2.5 | 4 | 6 | 8.8 | 12 | 16 | 22/24 | 28/30 | 34/39 | 44/45 | – | – | – | – | – | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | ||||||||||||||||||
Frequency | 0.01~120 Hz | ||||||||||||||||||
Voltage | 380~480V 3) | ||||||||||||||||||
Input ratings | Voltage | 3Ø380~480V (-15%~+10%) | |||||||||||||||||
Frequency | 50/60 Hz (± 5%) | ||||||||||||||||||
Protection degree | IP20 / UL Type1 | IP00 / UL Open 4) | |||||||||||||||||
Weight [kg (lbs.)] | Standard Type | 4.1 (9.0) | 4.2 (9.3) | 4.2 (9.3) | 4.9 (10.8) | 4.9 (10.8) | 6 (13.2) | 6 (13.2) | 12.5 (27.6) | 13 (28.7) | 20 (44.1) | 20 (44.1) | 27 (59.5) | 27 (59.5) | 29 (64) | 43 (94.8) | 42 (92.6) | ||
Built-in DCL Type | – | – | – | – | – | – | – | 19.5 (43.9) | 19.5 (42.9) | 26.5 (58.3) | 26.5 (58.3) | 39 (86) | 40 (88.2) | 42 (92.6) | 67 (147.4) | 68 (149.9) |
3-phase 400V Class (110~450kW)
Model Number (SVㅁㅁㅁiP5A-2) | 1100 | 1320 | 1600 | 2200 | 2800 | 3150 | 3750 | 4500 | |||
---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 178 | 210 | 259 | 344 | 436 | 488 | 582 | 699 | |||
Output ratings | Fan or pump load | Motor rating 2) | (HP) | 150 | 200 | 250 | 350 | 400 | 500 | 600 | 700 |
(kW) | 110 | 132 | 160 | 220 | 280 | 315 | 375 | 450 | |||
Current [A] | 223 | 264 | 325 | 432 | 547 | 613 | 731 | 877 | |||
(110% over current) | 110% 1 Minute (Normal Duty) | ||||||||||
General load | Motor rating | (HP) | 125 | 150 | 200 | 250 | 350 | 400 | 500 | 600 | |
(kW) | 90 | 110 | 132 | 160 | 220 | 280 | 315 | 375 | |||
Current [A] | 183 | 223 | 264 | 325 | 432 | 547 | 613 | 731 | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | ||||||||||
Frequency | 0.01~120 Hz | ||||||||||
Voltage | 380~480V 3) | ||||||||||
Input ratings | Voltage | 3Ø380~480V (-15%~+10%) | |||||||||
Frequency | 50/60 Hz (± 5%) | ||||||||||
Protection degree | IP00 / UL Open 4) | ||||||||||
DCL | Built-in | External Option | |||||||||
Weight [kg (lbs.)] | 101 (222.7) | 101 (222.7) | 114 (251.3) | 200 (441.9) | 200 (441.9) | 243 (535.7) | 380 (837.7) | 380 (837.7) |
3-phase 600V Class (5.5~110kW)
Model Number (SVㅁㅁㅁiP5A-2) | 055 | 075 | 110 | 150 | 185 | 220 | 300 | 370 | 450 | 550 | 750 | 900 | 1100 | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 9.6 | 12.7 | 19.1 | 23.9 | 31.1 | 35.9 | 48.6 | 59.8 | 72.5 | 87.6 | 121.1 | 145.8 | 178 | |||
Output ratings | Fan or pump load | Motor rating 2) | (HP) | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | 150 |
(kW) | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | |||
Current [A] | 9 | 12 | 17 | 23 | 27 | 34 | 43 | 55 | 64 | 80 | 104 | 128 | 150 | |||
(110% over current) | 110% 1Minute (Normal Duty) | |||||||||||||||
General load | Motor rating | (HP) | 5.5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | |
(kW) | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | |||
Current [A] | 6.1 | 9 | 12 | 17 | 23 | 27 | 34 | 43 | 55 | 64 | 80 | 104 | 128 | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | |||||||||||||||
Frequency | 0.01~120 Hz | |||||||||||||||
Voltage | 525 ~600V 3) | |||||||||||||||
Input ratings | Voltage | 3f 525~600V (-15% ~ +10 %) | ||||||||||||||
Frequency | 50/60 Hz (±5 %) | |||||||||||||||
Protection degree | IP20 / UL Type1 | IP00 / UL Open 4) | ||||||||||||||
Weight [kg (lbs.)] | 6.5 (14.4) | 7.0 (15.5) | 7.0 (15.5) | 11.7 (25.8) | 11.7 (25.8) | 18.9 (41.7) | 18.9 (41.7) | 32 (70.65) | 32 (70.65) | 32 (70.65) | 46 (101.5) | 46 (101.5) | 101 (223) |
1) Rated capacity (v 3 X V X I) is based on 220V for 200V class and 460V for 400V class.
2) Indicates the maximum applicable capacity when using a 4-Pole LS motor.
3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary.
4) IP20/UL Type1 with optional conduit, it can be modified to UL Type-1.