LS-Electric iS7 Drive

LS-Electric iS7 Drive – Find comprehensive resources for LS-Electric iS7 AC drives, including product catalogs, manuals, price list, programming guides, fault, alarm, warnings & software support. Get expert assistance for troubleshooting and optimization.

LS-Electric iS7 Drive image

The LS-Electric iS7 Drive is a high-performance variable frequency drive (VFD) designed for demanding industrial applications. Wide speed control range for versatile applications.

CatalogManual

Powerful Performance

  • Control mode: V/F, V/F PG, Sensorless Vector, Vector
  • Speed Control Range 1:100(Sensorless Vector), 1:1000(Vector)
  • LV Trip Delay Function, Cooling Fan Control
  • Droop Control, KEB Function, Flying Start, Flux Brake
  • PMSM Control

Flexibility

  • Built-in RS485 & Modbus Communication Profibus-DP,
  • DeviceNet, LonWorks, Rnet, Modbus TCP Option
  • Max. Input 11 Points, Output 6 Points when use expended I/O Card
  • PLC Card option: Master-K platform Normal Input 14 Points, Normal Output 7 points
  • Encoder Card option
  • Optional IP54 Enclosure (~ 22kW)

Convenience & Environment

  • Built-in EMC filter to protect from excessive electronic distortion
  • DC reactor built-in for harmonic reduction and power factor improvement
  • Widened graphic LCD keypad
  • Multi-language support (5 languages)
  • User & macro group support

3-phase 200V Class (0.75~22kW)

Type: SVㅁㅁㅁㅁiS7-2ㅁ0008001500220037005500750110015001850220
Motor Applied 1)VT[HP]2357.5101520253040
[kW]1.52.23.75.57.5111518.52230
CT[HP]12357.51015202530
[kW]0.751.52.23.75.57.5111518.522
Rated OutputRated Capacity [kVA] 2)1.93.04.56.19.112.217.522.928.233.5
Rated Current [A] 3)CT581216243246607488
VT81216243246607488124
Output Frequency [Hz]0~400 [Hz] 4)
Output Voltage [V]3-phase 200 ~ 230V 5) (Sensorless-1 : 0~300Hz, Sensorless-2, Vector : 0.1~120Hz)
Rated InputAvailable Voltage [V]3-phase 200 ~ 230 VAC (-15% ~ +10%)
Frepuency [Hz]50 ~ 60 [Hz] (±5%)
Rated Current [A]CT4.36.911.214.922.128.644.355.970.885.3
VT6.810.614.921.328.641.254.769.782.9116.1

3-phase 200V Class (30~375kW)

Type: SVㅁㅁㅁㅁ iS7-2ㅁ03000370045005500750
Motor Applied 1)VT[HP]506075100125
[kW]3745557590
CT[HP]40506075100
[kW]3037455575
Rated OutputRated Capacity [kVA] 2)46576984116
Rated Current [A] 3)CT116146180220288
VT146180220288345
Output Frequency0 ~ 400 [Hz] (Sensorless-1: 0 ~ 300Hz, Sensorless-2, Vector: 0 ~ 120Hz) 4)
Output Voltage [V]3-phase 200 ~ 230V 5)
Rated InputAvailable Voltage [V]3-phase 200 ~ 230VAC (-15% ~ +10%)
Frepuency [Hz]50 ~ 60 [Hz] (±5%)
Rated Current [A]CT121154/td>191233305
VT152190231302362

3-phsae 400V Class (0.75~22kW)

Type: SVㅁㅁㅁㅁ iS7-4ㅁ0008001500220037005500750110015001850220
Motor Applied 1)VT[HP]2357.5101520253040
[kW]1.52.23.75.57.5111518.52230
CT[HP]12357.51015202530
[kW]0.751.52.23.75.57.5111518.522
Rated OutputRated Capacity [kVA] 2)1.93.04.56.19.112.217.522.929.734.3
Rated Current [A] 3)CT2.5468121624303945
VT46812162430394561
Output Frequency0~400 [Hz] 4)
Output Voltage [V]3-phase 380 ~ 480V 5) (Sensorless-1 : 0~300Hz, Sensorless-2, Vector : 0.1~120Hz)
Rated InputAvailable Voltage [V]3-phase 380 ~ 480 VAC (-15% ~ +10%)
Frepuency [Hz]50 ~ 60 [Hz] (±5%)
Rated Current [A]CT2.23.65.57.511.014.422.026.635.641.6
VT3.75.77.711.114.721.926.435.541.155.7

3-phase 400V Class (30~375kW)

Type: SVㅁㅁㅁㅁ iS7-2ㅁ03000370045005500750090011001320160018502200285031503750
Motor Applied 1)VT[HP]506075100125150200250300350400500600700
[kW]3745557590110132160185220280315375450
CT[HP]40506075100125150200250300350400500600
[kW]303745557590110132160185220280315375
Rated OutputRated Capacity [kVA] 2)4657698411613917020248286329416467557
Rated Current [A] 3)CT617591110152183223264325370432547613731
VT7591110152183223264325370432547613731877
Output Frequency0 ~ 400 [Hz] (Sensorless-1: 0 ~ 300Hz, Sensorless-2, Vector: 0 ~ 120Hz) 4)
Output Voltage [V]3-phase 380 ~ 480V 5)
Rated InputAvailable Voltage [V]3-phase 380 ~ 480 VAC (-15% ~ +10%)
Frepuency [Hz]50 ~ 60 [Hz] (±5%)
Rated Current [A]CT55.567.982.4102.6143.4174.7213.5255.6316.3404466605674798
VT67.581.7101.8143.6173.4212.9254.2315.3359.3463590673796948

1) Applied ​motor ​indicates the maximum capacity applied for use of a standard 4-pole standard motor.

2) Rated Capacity: The input capacity of a 200V class is based on 220V and a 400V class is based on 440V. The current rating is based on the CT current.

3) The output of the rated current is limited according to the setting of the carrier frequency (CON-04).

4) The frequency can be set up to 300Hz by selecting 3, 4 Sensorless-1, or Sensorless-2 as the control mode (DRV-09 Control Mode).

5) The maximum output voltage does not go over the supplied power voltage. The preferred output voltage can be selected below the supplied power voltage.

* Non-DCR products are provided warranty service only when used in the CT (Heavy duty) load rating.