Nidec Control Techniques Commander C200 Drive – Find comprehensive resources for Nidec & Control Technique Commander C200 AC drives, including product catalogs, manuals, price list, programming guides, fault, alarm, warnings & software support. Get expert assistance for troubleshooting and optimization.

Nidec Control Techniques Commander C200 is a series of compact and cost-effective AC drives designed for general-purpose industrial applications. It’s part of the Commander C family, known for its simplicity and ease of use.
Power rating:
- 0.25 kW – 132 kW (0.33 hp to 200 hp)
- 100 V | 200 V | 400 V | 575 V | 690 V
Features
The Commander C200 delivers benchmark functionality at no added cost to the base drive itself. Plug-in options, dynamic performance, PLC functionality and other advanced features such as fieldbus, Ethernet, and Modbus RTU communications ensure that in more complex applications Commander C200 can deliver more than the average general purpose drive – giving you lower cost solutions and better productivity in your motor control applications.
- Simple and Compact: The C200 is designed to be small and easy to install, making it ideal for applications where space is limited.
- Ease of Use: These drives are known for their simple setup and commissioning. They typically have a basic keypad interface and straightforward documentation.
- Open Loop Vector Control (RFC-A): The C200 features advanced Rotor Flux Control (RFC-A) for excellent open-loop control of induction motors. This provides good performance without the need for feedback devices.
- Cost-Effective: The C200 is designed to be a highly cost-effective solution for general-purpose applications.
- Flexible Communication: The C200 offers various communication options through optional SI modules, including Ethernet, Modbus TCP, and various fieldbus interfaces. This facilitates seamless integration with automation systems.
- Onboard PLC: The C200 has an integrated PLC for basic logic control, reducing the need for external controllers in some applications.
Enhance up-time and system flexibility
- Flexible system integration and remote diagnostics through optional industrial
Ethernet and fieldbus communication - Flexible I/O expandable with SI-I/O option module
- Enhanced functionality and onboard PLC programming provide a low-cost system
solution, minimizing the need for additional equipment such as PLCs
Maximum machine productivity with exceptional open-loop motor control
- RFC-A (Rotor Flux Control) algorithm for high performance induction motor control
of demanding applications - Closed loop current control without a position feedback device
- Speed control for conveyors, fans, pumps, and mixers, where their function is
controlled remotely with fieldbus or Ethernet communications
Specifications
Motor Control
C200, C300: Induction Motors |
C300PM: Permanent Magnet Motors |
Control Mode
C200 | C300 | C300 PM | |
Open loop vector or V / Hz induction motor control | ✓ | ✓ | |
Open loop Rotor Flux Control for induction motors (RFC-A) | ✓ | ✓ | |
Sensorless permanent magnet motor control | ✓ |
Environment
Ambient Operating Temperature | Size 1 – 4: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. | Operation to 60°C (140°F) with de-rating Size 5 – 9: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. | Operation to 55°C (131°F) with de-rating |
Cooling Method | Forced convection |
Humidity | 95 % non-condensing at 40 °C (104 °F) |
Storage Temperature | Size 1 – 4: -40°C to 60°C (-40°F to 140°F) — 24 months Max. Size 5 – 9: -40°C to 55°C (-40°F to 131°F) — 24 months Max. |
Altitude | De-rate the continuous output current by 1% for every 100 m (328 ft) above 1000 m (3,280 ft) to a maximum of 3000 m (9,840 ft) |
Vibration | Tested in accordance with IEC 60068-2-64 and IEC 60068-2-6 |
Mechanical Shock | Tested in accordance with IEC 60068-2-27 and IEC 60068-2-29 |
Enclosure Rating | IP20, NEMA 1 conduit kits available |
Electromagnetic Capability | IEC/ EN 61800-3 Immunity and Emissions EN 61000-6-2: Immunity for industrial environments EN 61000-6-4: Emissions for industrial environmentsM/br> EN 61000-3-2: Harmonic current emissions An EMC data sheet is available on request |
RoHS | Complies with the Restriction of Hazardous Substances Directive (2011/65/EU) |
AC supply requirements
Voltage | 100 V to 120 V ±10 % 200 V to 240 V ±10 % 380 V to 480 V ±10 % 500 V to 575 V ±10 % 500 V to 690 V ±10 % |
Phase | 1Ø and 3Ø (Model dependent) |
Maximum Supply Imbalance | 2% negative phase sequence, 3% voltage imbalance between phases |
Input Frequency | 45 to 66 Hz |
Input Displacement Power Factor | 0.97 |
Control
Switching Frequency | Size 1 – 4: 0.667, 1, 2, 3, 4, 6, 8 12 & 16 kHz Size 5 – 9: 2, 3, 4, 6, 8 12 & 16 kHz |
Output Frequency Range | 0 to 550 Hz |
Frequency Accuracy | ±0.02% of full scale |
Frequency Resolution | 0.01 Hz |
Analog Input Resolution | Voltage mode: 11 bits (unipolar) Current mode: 11 bits |
Braking | Dynamic braking transistor included, requires external resistor |
Protection
DC Bus Undervoltage Trip | 100 V models: 175 Vdc 200 V models: 175 Vdc 400 V models: 330 Vdc 575 V models: 435 Vdc 690 V models: 435 Vdc |
DC Bus Overvoltage Trip | Frame sizes 1 – 4: 100 V models: 510 Vdc 200 V models: 510 Vdc 400V models: 870 Vdc |
Frame size 5 – 9: 200V models: 415 Vdc 400 V models: 830 Vdc 575 V models: 990 Vdc 690 V models: 1190 Vdc | |
Drive Overload Trip | Programmable: Default settings: 180% for 3s, 150% for 60s |
Instantaneous Overcurrent Trip | 220% of rated motor current |
Phase Loss Trip | DC bus ripple threshold exceeded |
Over-temperature Trip | Drive heatsink temperature exceeds 95°C (203°F) |
Short Circuit Trip | Protects against output phase-to-phase fault |
Ground Fault Trip | Protects against output phase-to-ground fault |
Motor Thermal Trip | Electronically protects the motor from overheating due to loading conditions |
Approval & listings
UL, cUL | UL file NMMS/8: E171230 |
CE | CE approval |
EU | These products comply with the Restriction of Hazardous Substances Directive (2011/65/EU), the Low Voltage Directive (2014/35/EU) and the Electromagnetic Compatibility Directive, (2014/30/EU). |
RCM | RCM Registered supplier No. 12003815281 |
ISO | Manufacturing facilities comply with ISO 9001:2015 and ISO 14001 |
TÜV | C300 models only: The Safe Torque Off (STO) function may be used as a safety component of a machine. Type examination certificates by TÜV Rheinland: Frame sizes 1 – 4: No. 01/205/5383.03/18 Frame sizes 5 – 9: No. 01/205/5387.02/18 Functional safety parameters: EN ISO 13849-1 – Cat 4, PLe EN61800-5-2/EN62061/IEC 61508 – SIL 3 UL functional safety approval: FSPC E171230 |