Nidec Control Techniques Commander C300 Drive

Nidec Control Techniques Commander C300 Drive – Find comprehensive resources for Nidec & Control Technique Commander C300 AC drives, including product catalogs, manuals, price list, programming guides, fault, alarm, warnings & software support. Get expert assistance for troubleshooting and optimization.

Nidec Control Techniques Commander C300 Drive image

Nidec Control Techniques Commander C300 is a series of compact and cost-effective AC drives designed for general-purpose industrial applications. It’s part of the Commander C family, known for its simplicity and ease of use.

Power rating:

  • 0.25 kW – 110 kW (0.33 hp to 200hp)
  • 100 V | 200 V | 400 V
CatalogManual
  • Simple and Compact: The C300 is designed to be small and easy to install, making it ideal for applications where space is limited.
  • Ease of Use: These drives are known for their simple setup and commissioning. They typically have a basic keypad interface and straightforward documentation.
  • Open Loop Vector Control (RFC-A): The C300 features advanced Rotor Flux Control (RFC-A) for excellent open-loop control of induction motors. This provides good performance without the need for feedback devices.
  • Integrated Safety: The C300 includes built-in dual Safe Torque Off (STO) inputs, certified to SIL3 / PLe. This allows for direct integration with safety systems, simplifying safety system design and reducing costs.
  • Flexible Communication: The C300 offers various communication options.
  • Onboard PLC: The C300 has an integrated PLC for basic logic control, reducing the need for external controllers in some applications.

Enhance up-time and system flexibility

  • Flexible system integration and remote diagnostics through optional industrial Ethernet and fieldbus communication
  • Flexible I/O that is expandable with SI-I/O option module
  • Enhanced functionality and onboard PLC programming provides a low-cost system solution, minimizing the need for additional equipment such as PLCs

High performance open loop motor control

  • RFC-A (Rotor Flux Control) algorithm for exceptional induction motor control
    of demanding applications
  • Closed loop current control without a position feedback device
  • Speed control for conveyors, fans, pumps, and mixers, where their function
    is controlled remotely with fieldbus or Ethernet communications

Communications

  • Snap-in SI-Modules for industry standard fieldbus, Ethernet or extended I/O options

Other

  • Two Safe Torque Off (STO) Inputs & Built-in PLC
  • Pumping: For controlling pumps in various industries.
  • Fans: For optimizing fan performance and energy efficiency.
  • Conveyors: For smooth and reliable material handling.
  • Mixers: For precise control of mixing processes.
  • Simple Machines: For general-purpose machine control.

Motor Control

C200, C300: Induction Motors 
C300PM: Permanent Magnet Motors

Control Mode

 C200C300C300 PM 
Open loop vector or V / Hz induction motor control ✓   ✓ 
Open loop Rotor Flux Control for induction motors (RFC-A) ✓  ✓ 
Sensorless permanent magnet motor control    ✓

Environment

Ambient Operating TemperatureSize 1 – 4: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. | Operation to 60°C (140°F) with de-rating
Size 5 – 9: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. | Operation to 55°C (131°F) with de-rating
Cooling MethodForced convection
Humidity95 % non-condensing at 40 °C (104 °F)
Storage TemperatureSize 1 – 4: -40°C to 60°C (-40°F to 140°F) — 24 months Max.
Size 5 – 9: -40°C to 55°C (-40°F to 131°F) — 24 months Max.
AltitudeDe-rate the continuous output current by 1% for every 100 m (328 ft) above 1000 m (3,280 ft) to a maximum of 3000 m (9,840 ft)
VibrationTested in accordance with IEC 60068-2-64 and IEC 60068-2-6
Mechanical ShockTested in accordance with IEC 60068-2-27 and IEC 60068-2-29
Enclosure RatingIP20, NEMA 1 conduit kits available
Electromagnetic CapabilityIEC/ EN 61800-3 Immunity and Emissions
EN 61000-6-2: Immunity for industrial environments
EN 61000-6-4: Emissions for industrial environmentsM/br> EN 61000-3-2: Harmonic current emissions
An EMC data sheet is available on request
RoHSComplies with the Restriction of Hazardous Substances Directive (2011/65/EU)

AC supply requirements

Voltage100 V to 120 V ±10 %
200 V to 240 V ±10 %
380 V to 480 V ±10 %
500 V to 575 V ±10 %
500 V to 690 V ±10 %
Phase1Ø and 3Ø (Model dependent)
Maximum Supply Imbalance2% negative phase sequence, 3% voltage imbalance between phases
Input Frequency 45 to 66 Hz
Input Displacement Power Factor0.97

Control

Switching FrequencySize 1 – 4: 0.667, 1, 2, 3, 4, 6, 8 12 & 16 kHz
Size 5 – 9: 2, 3, 4, 6, 8 12 & 16 kHz
Output Frequency Range 0 to 550 Hz
Frequency Accuracy±0.02% of full scale
Frequency Resolution 0.01 Hz
Analog Input Resolution Voltage mode: 11 bits (unipolar) Current mode: 11 bits
Braking Dynamic braking transistor included, requires external resistor

Protection

DC Bus Undervoltage Trip100 V models: 175 Vdc
200 V models: 175 Vdc
400 V models: 330 Vdc
575 V models: 435 Vdc
690 V models: 435 Vdc
DC Bus Overvoltage Trip Frame sizes 1 – 4:
100 V models: 510 Vdc
200 V models: 510 Vdc
400V models: 870 Vdc
Frame size 5 – 9:
200V models: 415 Vdc
400 V models: 830 Vdc
575 V models: 990 Vdc
690 V models: 1190 Vdc
Drive Overload TripProgrammable: Default settings: 180% for 3s, 150% for 60s
Instantaneous Overcurrent Trip 220% of rated motor current
Phase Loss Trip DC bus ripple threshold exceeded
Over-temperature Trip Drive heatsink temperature exceeds 95°C (203°F)
Short Circuit Trip Protects against output phase-to-phase fault
Ground Fault Trip Protects against output phase-to-ground fault
Motor Thermal Trip Electronically protects the motor from overheating due to loading conditions

Approval & listings

UL, cULUL file NMMS/8: E171230
CE CE approval
EU These products comply with the Restriction of Hazardous Substances Directive (2011/65/EU), the Low Voltage Directive (2014/35/EU) and the Electromagnetic Compatibility Directive, (2014/30/EU).
RCM RCM Registered supplier No. 12003815281
ISO Manufacturing facilities comply with ISO 9001:2015 and ISO 14001
TÜV C300 models only: The Safe Torque Off (STO) function may be used as a safety component of a machine. Type examination certificates by TÜV Rheinland:
Frame sizes 1 – 4: No. 01/205/5383.03/18
Frame sizes 5 – 9: No. 01/205/5387.02/18 Functional safety parameters:
EN ISO 13849-1 – Cat 4, PLe
EN61800-5-2/EN62061/IEC 61508 – SIL 3 UL functional safety approval: FSPC E171230