Power rating:

  • 1.1 kW to 2.8 MW
  • (1.5 hp to 4,200 hp)
  • 200 V / 400 V / 575 V / 690 V
CatalogManual

HVAC Drive H300 variable frequency AC drive (VFD) is the result of extensive research and builds on our vast experience of the HVAC market. The HVAC Drive H300 dimensions are among the smallest in its class at every power rating. This saves valuable building real estate, makes the drives easy to handle, and maximizes mounting flexibility.

A complete HVAC building automation solution

The HVAC Drive H300 is optimised for fan/compressor control in HVAC applications and has all the features you would expect from a dedicated HVAC drive and more:

Building Automation Systems

Seamless integration with Building Automation Systems with the following onboard communications supported:

  1. BACnet, conformance tested to guarantee reliable operation
  2. Modbus RTU communications

Custom Software

  • Flexibility without a Building Management System with optional modules for running custom application software.

Fire mode

  • The HVAC Drive H300 has onboard Fire mode which allows the drive to continue running uninterrupted in the event of a fire. It can allow the safe extraction of smoke while the drive’s other functions are maintained.

High efficiency operating modes

  • Quiet operation with Rotor Flux Control modes, high switching frequencies (up to 16 kHz).
  • Intelligent 10 speed drive cooling fan with minimum noise operation.

Conformal coated PCB

  • High product reliability with conformally coated PCBs as standard.

Compact dimensions

  • Among the most compact VFD in its class at every frame size, maximizing mounting flexibility.

Dual PID

  • Built-in dual process PID loops that can operate independently or be combined to provide more complex functionality.

Energy efficiency as standard

  • Exponential energy savings through fitting a Control Techniques Variable Frequency Drive into the application.
  • HVAC Drive H300 provides high energy efficiency, up to 98% where very little energy is lost in the conversion.
  • Motor control of super high efficiency sensor-less permanent magnet motors.
  • Dynamic Volts/Hertz energy optimization minimises power loss under low load conditions.

Energy Savings

Energy savings features promise a low total cost ownership:

  1. Sleep, Wake & VFD standby modes ensure minimal wasted energy
  2. Onboard power metering includes a cost per kWh function to track operating costs
  3. Energy savings verified with CT Energy Efficiency Calculator tool

Thermistor Monitoring

  • A temperature sensor input is available which can directly provide an analogue input without a transducer for control of fans and compressors. 

Extreme Operating Conditions

  • Operate in conditions from -20°C to 55°C* (40 °C as standard, above with derating).

Extended Connectivity

  • Extended connectivity with SI option modules (POWERLINK, EtherNet/IP, Modbus TCP/IP, PROFINET, PROFIBUS, DeviceNet and CANopen).

Quick Commissioning

HVAC Drive H300 portable memory devices:

  • A Smartcard enables simplified maintenance and commissioning without a PC, storing parameters and system upgrades.

HVAC Drive H300 ratings guide

200/240 Vac ±10%

DriveNormal Duty
Max
continuous
current (A)

Motor shaft
power (kW)
Motor shaft
power (hp) 
H300-03200066A10
6.6
1.1
1.5
H300-03200080A10
8
1.5
2
H300-03200110A10
11
2.2
3
H300-03200127A10
12.7
3
3
H300-04200180A10
18
4
5
H300-04200250A10
255.57.5
H300-05200300A10
307.510
H300-06200500A10
501115
H300-06200580A10
581520
H300-07200750A10
7518.525
H300-07200940A10
942230
H300-07201170A10
117
30
40
H300-08201490A10
149
37
50
H300-08201800A10
180
45
60
H300-09202160A10
216
55
75
H300-09202660A10
266
75
100
H300-09202160E10
216
55
75
H300-09202660E10
266
75
100
H300-10203250E10
325
90
125
H300-10203600E10
360
110
150

380/480 Vac ±10%

Drive
Normal Duty
Max
continuous
current (A)

Motor shaft
power (kW)

Motor shaft
power (hp)

H300-03400034A10
3.41.1
1.5
H300-03400045A104.5
1.5
2
H300-03400062A106.2
2.2
3
H300-03400077A10
7.7
3
5
H300-03400104A10
10.4
45
H300-03400123A10
12.35.5 7.5
H300-04400185A10
18.5
7.5
10
H300-04400240A10
24
11
15
H300-05400300A10 
30
15
20
H300-06400380A10
38
18.5
25
H300-06400480A10
48
22
30
H300-06400630A10
63
30
40
H300-07400790A10
79
37
50
H300-07400940A10
94
45
60
H300-07401120A10
112
55 
75
H300-08401550A10
155
75
100
H300-08401840A10
184
90
125
H300-09402210A10
221
110
150
H300-09402660A10 
266132
200
H300-09402210E10
221110
150
H300-09402660E10
266132
200
H300-10403200E10
320
160
250
H300-10403610E10
361
200
300
H300-11404370E10
437
225
350
H300-11404870E10
487
250
400
H300-11405070E10
507
280
450
H300-12404800TU0
608
315
500
H300-12405660TU0
 660355
550
H300-12406600TU0
755
400
650
H300-12407200TU0
8651
500
700

Note1: 110 % Overload at 30˚C and below and No Overload above that.

500/575 Vac ±10%

Drive
Normal Duty
Max
continuous
current (A)

Motor shaft
power (kW)
Motor shaft
power (hp)

H300-05500039A10
3.9
2.2
3
H300-05500061A10
6.1
4
5
H300-05500100A10
10
5.5
7.5
H300-06500120A10
12
7.5
10
H300-06500170A10
17
11
15
H300-06500220A10
22
15
20
H300-06500270A10
27
18.5
25
H300-06500340A10
34
22
30
H300-06500430A10
43
30
40
H300-07500530A10
53
37
50
H300-07500730A10
73
45
60
H300-08500860A10
86
55
75
H300-08501080A10
108
75
100
H300-09501250A10
125
90
125
H300-09501550A10
155
110
150
H300-09501250E10
125
90
125
H300-09501500E10
150110150
H300-10502000E10
200130200
H300-11502480E10
248175250
H300-11502880E10
288225300
H300-11503150E10
315250350
H300-12503150
376250350
H300-12503600
428300400
H300-12504100
480330450
H300-12504600
532370500

500/690 Vac ±10% 

Drive
Normal Duty
Max
continuous
current (A)

Motor shaft
power (kW)

Motor shaft
power (hp)

H300-07600230A10
23
18.5
25
H300-07600300A10
30
22
30
H300-07600360A10
36
30
40
H300-07600460A10
46
37
50
H300-07600520A10
52
45
60
H300-07600730A10
73
55
75
H300-08600860A10
86
75
100
H300-08601080A10
108 
90
125
H300-09601250A10
125
110
150
H300-09601500A10
150
132
175
H300-09601250E10
125
110 
150
H300-09601550E10
155
132
175
H300-10601720E10
172
160
200
H300-10601970E10
197
185
250
H300-11602250E10
225
200
250
H300-11602750E10
275
250
300
H300-11603050E10 
305
280
400
H300-12603150376355450
H300-12603600428400500
H300-12604100
480450600
H300-12604600
532500650

Normal duty operation only

Suitable for HVAC applications, with a current overload requirement of 110% for 60 s*.

Conformance

  • IP20 / NEMA1 / UL TYPE 1 *UL open class as standard, additional kit needed to achieve Type 1
  • IP65 / NEMA4 / UL TYPE 12 rating is achieved on the rear of the drive when through panel mounted
  • *Frame size 9D, 9E, 10D and 10E achieve IP55 / NEMA 4 / UL Type 12
  • Ambient temperature -20 °C to 40 °C (-4 °F to 104 °F) as standard. Up to 55 °C (131 °F) with derating
  • Humidity 95 % maximum (non-condensing) at 40 °C (104 °F)
  • Altitude: 0 to 3000 m (9900 ft), derate 1 % per 100 m (330 ft) between 1000 m (3300 ft) and 3000 m (9900 ft)
  • Random Vibration Tested in accordance with IEC 60068-2-64
  • Bump Tested in accordance with IEC 60068-2-29
  • Sinusoidal Vibration Tested in accordance with IEC 60068-2-6
  • Mechanical Shock Tested in accordance with IEC 60068-2-29
  • Storage temperature -40 °C to 55 °C (-40 °F to 131 °F) or up to 70°C (158 °F) for short-term storage
  • Electromagnetic Immunity complies with EN 61800-3 and EN 61000-6-2
  • With onboard EMC filter, emissions comply with EN 61800-3 (category C3)
  • EN 61000-6-3 and EN 61000-6-4 with optional footprint EMC filter
  • IEC 60146-1-1 Supply conditions (category C1 or C2 depending on rating)
  • IEC 61800-5-1 (Electrical Safety)
  • IEC 61131-2 I/O
  • EN 61000-3-12 with optional line reactor
  • UL 508C (Electrical Safety)

Dimensions

Frame size
Dimensions Weight
 mm (HxWxD)
in (HxWxD)
kg (lb)
3382 x 83 x 200
15.0 x 3.3 x 7.9
4.5 (9.9)
4391 x 124 x 200
15.4 x 4.9 x 7.9
6.5 (14.3)
5391 x 143 x 200
15.4 x 5.6 x 7.6
7.4 (16.3)
6391 x 210 x 227
15.4 x 8.3 x 8.9
14 (30.9)
7557 x 270 x 280
21.9 x 10.6 x 11.0
28 (61.7)
8803 x 310 x 290
31.6 x 12.2 x 11.4
50 (110.2)
9A1108 x 310 x 290
43.6 x 12.2 x 11.4
66.5 (146.6)
9E/10E1069 x 310 x 290
42.1 x 12.2 x 11.4
46 (101.4)
9D/10D
Rectifier
355 x 310 x 290
———————
Inverter
773 x 310 x 290
Rectifier
15.8 x 12.2 x 11.4
———————–
Inverter
30.4 x 12.2 x 11.4
12 (26.5)
———————–
34 (75)
11E
1242 x 310 x 312
48.9 x 12.2 x 12.3
63 (138.9)
12
1750 x 295 x 526
68.9 x 11.6 x 20.7
AC to AC (‘T’ type): 130 kg (287 lb)
DC to AC (‘D’ type): 113 kg (249 lb)

*For more detailed information please see technical documents.