LS-Electric XBC/XEC H-Type – Find comprehensive resources for LS-Electric XBC/XEC H-Type PLC & controller, including product catalogs, manuals, price list, programming guides, fault, alarm, warnings & software support. Get expert assistance for troubleshooting and optimization.
The LS Electric XBC/XEC H-Type PLC is a high-performance model within the XGB series of micro PLCs. It’s designed for more demanding automation applications that require higher processing speeds, more memory, and advanced features.
Performance specifications
Item | XBC/XEC-DR32H XBC-DR32H/ DC*1) XEC-DR32H / DI | XBC/XEC-DN32H XEC-DP32H*1) XBC-DN32H / DC | XBC/XEC-DR64H XBC-DR64H/ DC*1) XEC-DR64H / DI | XBC/XEC-DN64H XEC-DP64H*1) XBC-DN64H / DC |
---|---|---|---|---|
Control method | Repetitive, cyclic, interrupt, constant scan | |||
I/ O control method | Refresh mode (Batch processing by scan synchronization), Direct mode by instruction | |||
Programming language | Ladder diagram or IEC standard (LD, SFC, ST)*1) | |||
Processing speed | 83 ns / Step | |||
Program capacity | 15Kstep (IEC type: 200KB) | |||
Main unit I /O points | 32 (Input:16, Output:16) | 32 (Input:16, Output:16) | 64 (Input: 32, Output: 32) | 64 (Input: 32, Output: 32) |
Max. I /O points (Main + Expansion 10 stages) | 352 points | 384 points | ||
Total program | 128 | |||
Operation mode | RUN, STOP, DEBUG | |||
Self diagnosis | Detects errors of scan time, memory error, I/O error, battery error, power error, etc. | |||
Program port | USB (Rev 1.1), RS-232C 1 channel (Loader) | |||
Retain data at power failure | Latch area setting at basic parameter | |||
Built-in functions | RS-232C / RS-485 (2 ch), Pulse catch, Input filter, External interrupt, PID control, High-speed counter, Positioning, RTC |
Data memory | ||||
---|---|---|---|---|
XBC | XEC (IEC type) | |||
P | P0000 ~ P1023F (16,384 points) | Symbolic variable | A | 32KB (Max. 16KB retain setting available) |
M | M0000 ~ M1023F (16,384 points) | Input variable | I | 2KB (%IX 15.15.63) |
K | K0000 ~ K4095F (65,536 points) | Output variable | Q | 2KB (%QX 15.15.63) |
L | L0000 ~ L2047F (32,768 points) | Direct variable | M | 16KB (Max. 8KB retain setting available) |
F | F0000 ~ F1023F (16,384 points) | R | 20KB (1 block) | |
T | 100ms, 10ms, 1ms: T0000 ~ T1023 (1,024)(Adjustable by parameter setting) | W | 20KB | |
C | C0000 ~ C1023 (1,024) | Flag variable | F | 2KB |
S | S00.00 ~ S127.99 | K | 8KB | |
D | D0000 ~ D10239 (10,240 word) | L | 4KB | |
U | U00.00 ~ U0A.31 (Analog data refresh area: 352 word) | N | 10KB | |
Z | Z000 ~ Z127 (128 word) | U | 1KB | |
N | N000 ~ N5119 (5,120 word) | Flash area | R | 20KB (2 blocks) |
*1) XEC is IEC standard language programming.
Input specification
Item | XBC/XEC- DR32H | XBC/XEC-DN32H XEC-DP32H | XBC/XEC- DR64H | XBC/XEC-DN64H XEC-DP64H | XEC-DR32H / D1 XEC-DR64H / D1 | |
---|---|---|---|---|---|---|
Input points | 16 points | 32 points | 16 points | |||
Rated input voltage | DC 24V | DC 12 / 24V | ||||
Rated input current | 4mA (Contact 0~7: 9mA) | 5 /10mA (Contact 0~7 : 7/15mA) | ||||
Operation voltage range | DC 20.4 ~ 28.8V (Ripple rate < 5%) | DC 9.5~30V (Ripple rate < 5%) | ||||
On voltage / On current | DC 19V or more/3mA or more | DC 9V or more/3mA or more | ||||
Off voltage / Off current | DC 6V or less/1mA or less | DC 5V or less/1mA or less | ||||
Input resistance | 5.6k Ω (P00 ~ P07: 2.7k Ω ) | 2.7k Ω (%IX0.0.0~%IX0.0.7:1.8k Ω ) | ||||
Response time | Off → On | 1/3/5/10/20/70/100 ms (Setting by CPU parameter) Initial value: 3ms | ||||
On → Off |
Relay output specification
Item | XBC/XEC- DR32H | XBC/ XEC- DR64H | |
---|---|---|---|
Output point | 16 points | 32 points | |
Insulation method | Relay insulation | ||
Rated load voltage / current | DC 24V 2A (Resistive load)/AC 220V 2A (COSø = 1), 5A/COM | ||
Min. load voltage / current | DC 5V/1mA | ||
Max. load voltage | AC 250V, DC 125V | ||
Off leakage current | 0.1mA (AC 220V, 60Hz) | ||
Service life | Mechanical | 20millions times or more | |
Electrical | Rated load voltage/current 100,000 times or more | ||
AC 200V/1.5A, AC 240V/1A (COSø = 0.7) 100,000 times or more | |||
AC 200V/1A, AC 240V/0.5A (COSø = 0.35) 100,000 times or more | |||
DC 24V/1A, DC 100V/0.1A (L / R = 7ms) 100,000 times or more | |||
Response time | Off → On | 10ms or less | |
On → Off | 12ms or less | ||
Common method | 4 points/COM | P20 ~ 2F: 4 points/COM P30 ~ 3F: 8 points/COM |
Transistor output specification
Item | XBC- DN32H / XEC- DN(P)32H | XBC- DN64H / XEC- DN(P)64H | |
---|---|---|---|
Output point | 16 points | 32 points | |
Insulation method | Photo coupler insulation | ||
Rated load voltage | DC 12/24V | ||
Load voltage range | DC 10.2 ~ 26.4 V | ||
Max. load voltage | 0.5A / 1point (P20 ~ 23: 0.1A/point) | ||
Off leakage current | 0.1mA or less | ||
Max. inrush current | 4A/10ms or less | ||
Max. voltage drop (On) | DC 0.4V or less | ||
Surge absorber | Zener Diode | ||
Response time | Off → On | 1ms or less | |
On → Off | 1ms or less (Rated load, resistive load) | ||
Common method | 4 points/COM | P20 ~ 2F: 4 points/COM P30 ~ 3F: 8 points/COM | |
External power supply | Voltage | DC 12/24V ±10% (Ripple voltage 4 Vp-p or less) | |
Current | 10mA or less (DC 24V connection) |