F153 fault in WEG CFW900 Drive

F153 fault in WEG CFW900 Drive indicates a Power Internal Air Overtemperature. This means the ambient air inside the drive exceeded critical limits, triggering a protective shutdown.
Cause:

Internal air overtemperature fault.

  • High ambient temperature around the inverter (>50 °C) and high output current.
  • Defective internal cooling fan (when applicable).

Remedy:

Check local cooling conditions, clear air blockages, and ensure cabinet fans are running correctly.