CodeCauseSolution
A2001
OVERCURRENT
Output current limit controller is active.Check motor load.
Check acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2).
Check motor and motor cable (including phasing).
Check ambient conditions.
A2002
OVERVOLTAGE
DC overvoltage controller is active.Check deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2).
Check input power line for static or transient overvoltage.
A2003
UNDERVOLTAGE
DC undervoltage controller is active.Check input power supply.
A2004
DIRLOCK
Change of direction is not allowed.Check parameter 1003 DIRECTION settings.
A2006
AI1 LOSS
Analog input AI1 signal has fallen
below limit defined by parameter
3021 AI1 FAULT LIMIT.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
A2009
DEVICE OVERTEMP
Drive IGBT temperature is excessive. Alarm limit is 120 °C.Check ambient conditions.
Check air flow and fan operation.
Check motor power against drive power.
A2010
MOTOR TEMP
Motor temperature is too high (or
appears to be too high) due to
excessive load, insufficient motor
power, inadequate cooling or
incorrect start-up data.
Check motor ratings, load and cooling.
Check start-up data.
Check fault function parameter settings.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
A2011
UNDERLOAD
Motor load is too low due to, for
example, release mechanism in
driven equipment.
Check for problem in driven equipment.
Check fault function parameter settings.
Check motor power against drive power.
A2012
MOTOR STALL
Motor is operating in stall region
due to, for example, excessive
load or insufficient motor power.
Check motor load and drive ratings.
Check fault function parameter settings.
A2013
AUTORESET
Automatic reset alarmCheck parameter group 31 AUTOMATIC
RESET settings.
A2017
OFF BUTTON
Drive stop command has been
given from control panel when
local control lock is active.
Disable the local control mode lock by
parameter 1606 LOCAL LOCK and retry.
A2018
PID SLEEP
Sleep function has entered the
sleeping mode.
See parameter group 40 PROCESS PID
SET 1.
F0001
OVERCURRENT
Output current has exceeded trip
level.
Overcurrent trip limit for drive is
325% of drive nominal current.
Check motor load.
Check acceleration time (parameters 2202
ACCELER TIME 1 and 2205 ACCELER TIME 2).
Check motor and motor cable (including phasing).
Check ambient conditions. Load capacity decreases
if installation site ambient temperature exceeds
40°C.
F0002 DC OVERVOLTExcessive intermediate circuit DC
voltage. DCovervoltage trip limit is
420 V for 200 V drives and 840V
for 400 V drives.
Check that overvoltage controller is on (parameter
2005 OVERVOLT CTRL).
Check brake chopper and resistor (if used). DC
overvoltage control must be deactivated when brake
chopper and resistor are used.
Check deceleration time (parameters 2203
DECELER TIME 1 and 2206 DECELER TIME 2).
Check input power line for static or transient
overvoltage.
Retrofit frequency converter with brake chopper and
brake resistor.
F0003
DEV OVERTEMP
Drive IGBT temperature is
excessive. Fault trip limit is
135°C.
Check ambient conditions.
Check air flow and fan operation.
Check motor power against drive power
F0004
SHORT CIRCUIT
Short circuit in motor cable(s) or
motor
Check motor and motor cable.
F0006
DC UNDERVOLT
Intermediate circuit DC voltage is
not sufficient due to missing input
power line phase, blown fuse,
rectifier bridge internal fault or too
low input power.
Check that undervoltage controller is on (parameter
2006 UNDERVOLT CTRL).
Check input power supply and fuses.
F0009
MOTOR OVERTEMP
Motor temperature is too high (or
appears to be too high) due to
excessive load, insufficient motor
power, inadequate cooling or
incorrect start-up data.
Check motor ratings, load and cooling.
Check start-up data.
Check fault function parameter settings.
Let motor cool down. Ensure proper motor cooling:
Check cooling fan, clean cooling surfaces, etc.
F0012
MOTOR STALL
Motor is operating in stall region
due to, for example, excessive
load or insufficient motor power.
Check motor load and drive ratings.
Check fault function parameter settings.
F0016
EARTH FAULT
Drive has detected earth (ground)
fault in motor or motor cable.
Check motor.
Check motor cable. Motor cable length must not
exceed maximum specifications.
Note: Disabling earth fault (ground fault) may
damage drive.
F0017
UNDERLOAD
Motor load is too low due to, for
example, release mechanism in
driven equipment.
Check for problem in driven equipment.
Check fault function parameter settings.
Check motor power against drive power.

Other useful link of ABB ACS150 Drive

Manual ProgrammingFault & AlarmParameter
RepairingBrake chopperBrake ResistorApplications
Control & Power WiringEMC FilterDimension & weightTechnical data
FeaturesMacroRating & Frame SizeDrive Part code Detail
Input Choke Output ChokeFuses Drive free Space
CoolingOptional Accessories Commissioning Cable Size
Switching FrequencyDe-ratingNoiseCable Length

Other Useful Link




abb acs150

Dedicated Free Forum & Chat Support

Get all fault, alarm, warning & error code solution at one place. Ask expert for support regarding programming, parameter & application selection and all information.


Other ABB Drive Series

Get all information of other ABB drives like product information, price list, programming, fault & error codes and all other information.


ABB Drives Price List image

ABB Drive Price List

ABB Drives Price List – compare drives by specification, rating, features & advance options. Get all information about drive like features, function, specification compare all drive. Here you can easily find drive as per application & features.


drive training image

Get free drive training, learn more about drive like –

What is drive ?

Types of drive

Working

Drive programming and many more


Get more information about Industrial Automation

Get all information about industrial automation like electronics & electrical basics, tools and test equipment’s, troubleshoot fault, learn repairing at card level & component level, learn more about devices like drives, PLC’s, soft-starter, sensor and many more.

click2electro learning image

Easily integrated drives for a wide range of applications – The silent operation mode adjusts the switching frequency of the drive to a higher level after the high-torque start, resulting in lower audible noise. The Flash-Drop tool provides a quick and safe way to configure multiple drives for identical mixer applications.

User-friendly LCD control panel and integrated potentiometer easy to use as per your application.

Powerful Tool for product finder – Search all industrial product, search by brand, search by series, search by part no. search by specification. Compare product by specification & options. Product filter – easy tool to filter your product for best match. Powerful product finder tool get your application compatible product with all solution like document & catalog, programming error and fault solution

Industrial Automation Forum – Forum with all your need, get support regarding application selection, application solution, product finder, product related problem solution. If any fault coming in your product simple search and get solution. If any fault or error not showing simple ask to our expert for best solution. Here you can search all fault, alarm & warning solution just simple search. No need to download multiple manual for multiple product.

Home | Join us on Facebook, Twitter, YouTube, Instagram, Quora, Reddit, LinkedIn, Pintereset, Blogger.