Delta C2000 VFD Parameter Setup Guide

Delta C2000 VFD Parameter Setup Guide – Easily configure your Delta C2000 series drive with this quick-reference parameter guide. Learn how to set motor data, frequency sources, and run commands.

Delta C2000 Series VFD: Essential Parameter Setup Guide

Configuring the correct parameters is crucial for the efficient operation of your Delta C2000 drive. Below is a list of the most common parameters used for initial setup and basic operation.

1. Quick Start & Factory Reset

Before programming, it is often helpful to reset the drive to factory defaults to clear any previous configurations.

  • 00-02 (Factory Reset): Set to 9 to reset all parameters to factory defaults (50Hz or 60Hz depending on your region).

2. Basic Motor Setup

Ensure these parameters match the information found on your motor’s nameplate to prevent damage and ensure performance.

  • 01-00 (Max Output Frequency): Set to the maximum frequency (e.g., 50Hz or 60Hz).
  • 01-01 (Max Voltage Frequency): Typically set to 50Hz or 60Hz.
  • 01-02 (Max Output Voltage): Set to match your motor’s rated voltage.

3. Command & Frequency Sources

Use these settings to define how you start, stop, and control the speed of your motor.

  • 00-20 (Source of Frequency Command):
    • 0: Digital Keypad
    • 2: Analog Input (Potentiometer)
  • 00-21 (Source of Operation Command):
    • 0: Digital Keypad (Run/Stop buttons)
    • 1: External Terminals (Push buttons/Switches)

4. Acceleration & Deceleration

  • 01-09 (Acceleration Time 1): Time in seconds to reach max frequency.
  • 01-10 (Deceleration Time 1): Time in seconds to stop from max frequency.

Important Programming Tips

  • Enter/Save: Always press the Enter key after changing a value to save the setting. The display will show “End” when saved.
  • Navigation: Use the Menu key to access parameter groups and the Up/Down arrows to scroll through parameters.
  • Safety: Always ensure the motor is at a complete stop before changing critical motor parameters.

Delta C2000 VFD Parameter List

Below list show Delta C2000 VFD Parameter List:

Factory Reset      
  00-02 9  
       
Motor Data      
  05–01 ……A  
  05–02 ……KW  
  05–03 ……rpm  
       
ID Run 05–00 0 No function
    1 Simple rolling auto-tuning for induction motor
    2 Static auto-tuning for induction motor
    5 Rolling auto-tuning for PM (IPM / SPM)
    12 FOC sensorless inertia estimation
       
Start/Stop      
  00–21 0 Digital keypad
    1 External terminals
    2 RS-485 communication input
    3 CANopen communication card
       
Control Mode      
  00–11 1 Scaler
    5 Vector
       
Stop Mode      
  00–22 0 Ramp
    1 Coast
       
2-wire/3wire 02–00 1 2-wire
    3 3-wire
       
Speed Reference    
  00–20 0 0: Digital keypad
    1 RS-485 communication input
    2 External analog input (Refer to Pr.03-00)
    3 External UP / DOWN terminal
    6 CANopen communication card
    8 Communication card
       
Motor pot 02–07 19 Digital up command MI7
  02–08 20 Digital down command MI8
       
Acc/Dec Time      
  01–12 ……s Acceleration Time 
  01–13 ……s Deceleration Time
       
Relay Output      
RO1 02–13 1 Indication during RUN
    11 Malfunction indication
    9 Drive is ready
       
RO2 02–13 1 Indication during RUN
    11 Malfunction indication
    9 Drive is ready