Code | Cause | Solution |
---|---|---|
A2001 OVERCURRENT | Output current limit controller is active. | Check motor load. Check acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). Check motor and motor cable (including phasing). Check ambient conditions. |
A2002 OVERVOLTAGE | DC overvoltage controller is active. | Check deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2). Check input power line for static or transient overvoltage. |
A2003 UNDERVOLTAGE | DC undervoltage controller is active.Check input power supply. | |
A2004 DIRLOCK | Change of direction is not allowed. | Check parameter 1003 DIRECTION settings. |
A2006 AI1 LOSS | Analog input AI1 signal has fallen below limit defined by parameter 3021 AI1 FAULT LIMIT. | Check fault function parameter settings. Check for proper analog control signal levels. Check connections. |
A2009 DEVICE OVERTEMP | Drive IGBT temperature is excessive. Alarm limit is 120 °C. | Check ambient conditions. Check air flow and fan operation. Check motor power against drive power. |
A2010 MOTOR TEMP | Motor temperature is too high (or appears to be too high) due to excessive load, insufficient motor power, inadequate cooling or incorrect start-up data. | Check motor ratings, load and cooling. Check start-up data. Check fault function parameter settings. Let motor cool down. Ensure proper motor cooling: Check cooling fan, clean cooling surfaces, etc. |
A2011 UNDERLOAD | Motor load is too low due to, for example, release mechanism in driven equipment. | Check for problem in driven equipment. Check fault function parameter settings. Check motor power against drive power. |
A2012 MOTOR STALL | Motor is operating in stall region due to, for example, excessive load or insufficient motor power. | Check motor load and drive ratings. Check fault function parameter settings. |
A2013 AUTORESET | Automatic reset alarm | Check parameter group 31 AUTOMATIC RESET settings. |
A2017 OFF BUTTON | Drive stop command has been given from control panel when local control lock is active. | Disable the local control mode lock by parameter 1606 LOCAL LOCK and retry. |
A2018 PID SLEEP | Sleep function has entered the sleeping mode. | See parameter group 40 PROCESS PID SET 1. |
F0001 OVERCURRENT | Output current has exceeded trip level. Overcurrent trip limit for drive is 325% of drive nominal current. | Check motor load. Check acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). Check motor and motor cable (including phasing). Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40°C. |
F0002 DC OVERVOLT | Excessive intermediate circuit DC voltage. DCovervoltage trip limit is 420 V for 200 V drives and 840V for 400 V drives. | Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL). Check brake chopper and resistor (if used). DC overvoltage control must be deactivated when brake chopper and resistor are used. Check deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2). Check input power line for static or transient overvoltage. Retrofit frequency converter with brake chopper and brake resistor. |
F0003 DEV OVERTEMP | Drive IGBT temperature is excessive. Fault trip limit is 135°C. | Check ambient conditions. Check air flow and fan operation. Check motor power against drive power |
F0004 SHORT CIRCUIT | Short circuit in motor cable(s) or motor | Check motor and motor cable. |
F0006 DC UNDERVOLT | Intermediate circuit DC voltage is not sufficient due to missing input power line phase, blown fuse, rectifier bridge internal fault or too low input power. | Check that undervoltage controller is on (parameter 2006 UNDERVOLT CTRL). Check input power supply and fuses. |
F0009 MOTOR OVERTEMP | Motor temperature is too high (or appears to be too high) due to excessive load, insufficient motor power, inadequate cooling or incorrect start-up data. | Check motor ratings, load and cooling. Check start-up data. Check fault function parameter settings. Let motor cool down. Ensure proper motor cooling: Check cooling fan, clean cooling surfaces, etc. |
F0012 MOTOR STALL | Motor is operating in stall region due to, for example, excessive load or insufficient motor power. | Check motor load and drive ratings. Check fault function parameter settings. |
F0016 EARTH FAULT | Drive has detected earth (ground) fault in motor or motor cable. | Check motor. Check motor cable. Motor cable length must not exceed maximum specifications. Note: Disabling earth fault (ground fault) may damage drive. |
F0017 UNDERLOAD | Motor load is too low due to, for example, release mechanism in driven equipment. | Check for problem in driven equipment. Check fault function parameter settings. Check motor power against drive power. |
Other useful link of ABB ACS150 Drive
Other Useful Link

Dedicated Free Forum & Chat Support
Get all fault, alarm, warning & error code solution at one place. Ask expert for support regarding programming, parameter & application selection and all information.
Other ABB Drive Series
Get all information of other ABB drives like product information, price list, programming, fault & error codes and all other information.


ABB Drive Price List
ABB Drives Price List – compare drives by specification, rating, features & advance options. Get all information about drive like features, function, specification compare all drive. Here you can easily find drive as per application & features.

Get free drive training, learn more about drive like –
What is drive ?
Types of drive
Working
Drive programming and many more
Get more information about Industrial Automation
Get all information about industrial automation like electronics & electrical basics, tools and test equipment’s, troubleshoot fault, learn repairing at card level & component level, learn more about devices like drives, PLC’s, soft-starter, sensor and many more.

Easily integrated drives for a wide range of applications – The silent operation mode adjusts the switching frequency of the drive to a higher level after the high-torque start, resulting in lower audible noise. The Flash-Drop tool provides a quick and safe way to configure multiple drives for identical mixer applications.
User-friendly LCD control panel and integrated potentiometer easy to use as per your application.
Powerful Tool for product finder – Search all industrial product, search by brand, search by series, search by part no. search by specification. Compare product by specification & options. Product filter – easy tool to filter your product for best match. Powerful product finder tool get your application compatible product with all solution like document & catalog, programming error and fault solution
Industrial Automation Forum – Forum with all your need, get support regarding application selection, application solution, product finder, product related problem solution. If any fault coming in your product simple search and get solution. If any fault or error not showing simple ask to our expert for best solution. Here you can search all fault, alarm & warning solution just simple search. No need to download multiple manual for multiple product.