bLF [Brake Control] fault in Schneider ATV930 drive
Cause: Brake release current not reached.
The torque set point is not reached.
The fluxing current is not stable.
Remedy:
- Verify the drive/motor connection.
- Verify the motor windings.
- Verify the [Brk Release Current] Ibr and [Brake release I Rev] Ird settings.