ALARM 38 Internal Fault fault in Danfoss FC301 drive

ALARM 38 Internal Fault fault in Danfoss FC301 drive

Cause: When an internal fault occurs, a code number defined in below table.

Troubleshooting:

– Cycle power.
– Check that the option is properly installed.
– Check for loose or missing wiring.
– It may be necessary to contact the Danfoss supplier or service department. Note the code number for further troubleshooting directions.

0: The serial port cannot be initialized. Contact the Danfoss supplier or Danfoss service department.
256–258: The power EEPROM data is defective or too old. Replace the power card.
512–519: Internal fault. Contact the Danfoss supplier or Danfoss service department.
783: Parameter value outside of minimum/maximum limits.
1024–1284: Internal fault. Contact the Danfoss supplier or Danfoss service department.
1299: The option software in slot A is too old.
1300: The option software in slot B is too old.
1302: The option software in slot C1 is too old.
1315: The option software in slot A is not supported/allowed.
1316: The option software in slot B is not supported/ allowed.
1318: The option software in slot C1 is not supported/ allowed.
1379–2819: Internal fault. Contact the Danfoss supplier or Danfoss service department.
1792: Hardware reset of digital signal processor.
1793: Motor-derived parameters not transferred correctly to the digital signal processor.
1794: Power data not transferred correctly at power-up to the digital signal processor.
1795: The digital signal processor has received too many unknown SPI telegrams. The AC drive also uses this fault code if
– the: MCO does not power up correctly. This situation can occur due to poor EMC protection or improper grounding.
1796: RAM copy error.
2561: Replace the control card.
2820: LCP stack overflow.
2821: Serial port overflow.
2822: USB port overflow.
3072–5122: Parameter value is outside its limits.
5123: Option in slot A: Hardware incompatible with the control board hardware.
5124: Option in slot B: Hardware incompatible with the control board hardware.
5125: Option in slot C0: Hardware incompatible with the control board hardware.
5126: Option in slot C1: Hardware incompatible with the control board hardware.
5376– 6231: Internal fault. Contact the Danfoss supplier or Danfoss service department.