0x00780007 Control card is defect (VCC15 neg.) fault in Lenze 9400 highline drive Cause: Device error. Remedy: Consultation with Lenze required.
Latest News & Article For Industrial Automation
0x00780006 Control card is defect (UB8) fault in Lenze 9400 highline drive
0x00780006 Control card is defect (UB8) fault in Lenze 9400 highline drive Cause: Device error. Remedy: Consultation with Lenze required.
0x00780005 Control card is defect (VCC15) fault in Lenze 9400 highline drive
0x00780005 Control card is defect (VCC15) fault in Lenze 9400 highline drive Cause: Device error. Remedy: Consultation with Lenze required.
0x00780004 Control card is defect (UB24) fault in Lenze 9400 highline drive
0x00780004 Control card is defect (UB24) fault in Lenze 9400 highline drive Cause: Device error. Remedy: Consultation with Lenze required.
0x00780003 Motor load I²xt > C00120 fault in Lenze 9400 highline drive
0x00780003 Motor load I²xt > C00120 fault in Lenze 9400 highline drive Cause: Motor is thermally overloaded, e.g. due to impermissible continuous current or frequent/long acceleration. Remedy: Check drive dimensioning. Check setting in C00120.
0x00780002 Motor load I²xt > C00127 fault in Lenze 9400 highline drive
0x00780002 Motor load I²xt > C00127 fault in Lenze 9400 highline drive Cause: Motor is thermally overloaded, e.g. due to impermissible continuous current or frequent/long acceleration. Remedy: Check drive dimensioning. Check setting in C00127.
0x00780001 Device utilisation Ixt > 100 % fault in Lenze 9400 highline drive
0x00780001 Device utilisation Ixt > 100 % fault in Lenze 9400 highline drive Cause: Frequent and too long acceleration processes with overcurrent. Remedy: Check drive dimensioning.
0x00780000 Device utilisation Ixt > C00123 fault in Lenze 9400 highline drive
0x00780000 Device utilisation Ixt > C00123 fault in Lenze 9400 highline drive Cause: Frequent and too long acceleration processes with overcurrent > C00123. Remedy: Check drive dimensioning.
0x00770011 Inside the device Fan is defective fault in Lenze 9400 highline drive
0x00770011 Inside the device: Fan is defective fault in Lenze 9400 highline drive Cause: Speed of internal fan is too low, e.g. due to dirt. Remedy: Check/clean fan.
0x00770010 Heatsink Fan is defect fault in Lenze 9400 highline drive
0x00770010 Heatsink: Fan is defect fault in Lenze 9400 highline drive Cause: Speed of heatsink fan too low, e.g. due to dirt. Remedy: Check/clean fan.