F40836 CX32 DRIVE-CLIQ: Send error for DRIVE-CLIQ data fault in Siemens SINAMICS G130 Drive Cause:A DRIVE-CLiQ communications error has occurred. Data were not able to be sent. Telegram type does not match send list. Remedy:Carry out a POWER ON (switch-off/switch-on).
Category: Faults & Alarm
Faults & Alarm – Get all brand fault, alarm, warning & error code solutions at one place. Expert guides to diagnosing & resolving industrial equipment faults and alarms. Get step-by-step solutions for common error codes & system alerts.
F40837 CX32 DRIVE-CLiQ: Component fault fault in Siemens SINAMICS G130 Drive
F40837 CX32 DRIVE-CLiQ: Component fault fault in Siemens SINAMICS G130 Drive Cause:Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded. Fault causes include errors in the telegram header and buffer memory. Remedy: Check the DRIVE-CLiQ wiring. Check the electrical cabinet design and cable routing for EMC compliance. If required, use another DRIVE-CLiQRead more ⟶
F40845 CX32 DRIVE-CLIQ: Cyclic data transfer error fault in Siemens SINAMICS G130 Drive
F40845 CX32 DRIVE-CLIQ: Cyclic data transfer error fault in Siemens SINAMICS G130 Drive Cause:A DRIVE-CLiQ communications error has occurred. Synchronization error during alternating cyclic data transfer. Remedy:Carry out a POWER ON (switch-off/switch-on).
F40851 CX32 DRIVE-CLIQ (CU): Sign-of-life missing fault in Siemens SINAMICS G130 Drive
F40851 CX32 DRIVE-CLIQ (CU): Sign-of-life missing fault in Siemens SINAMICS G130 Drive Cause:A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit. The DRIVE-CLiQ component did not set the sign-of-life to the Control Unit. Remedy:Upgrade the firmware of the component involved.
F40860 CX32 DRIVE-CLiQ (CU): Telegram error fault in Siemens SINAMICS G130 Drive
F40860 CX32 DRIVE-CLiQ (CU): Telegram error fault in Siemens SINAMICS G130 Drive Cause:A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit. Multiple fault causes are listed relating to checksum errors, telegram length, addressing, and timing. Remedy: Carry out a POWER ON (switch-off/switch-on). Check the electrical cabinet design and cableRead more ⟶
F40875 CX32 DRIVE-CLIQ (CU): Supply voltage failed fault in Siemens SINAMICS G130 Drive
F40875 CX32 DRIVE-CLIQ (CU): Supply voltage failed fault in Siemens SINAMICS G130 Drive Cause:The DRIVE-CLiQ communication signals that the supply voltage has failed. Remedy: Carry out a POWER ON (switch-off/switch-on). Check the supply voltage wiring of the DRIVE-CLiQ component. Check the dimensioning of the DRIVE-CLiQ component power supply.
F40885 CX32 DRIVE-CLIQ (CU): Cyclic data transfer error fault in Siemens SINAMICS G130 Drive
F40885 CX32 DRIVE-CLIQ (CU): Cyclic data transfer error fault in Siemens SINAMICS G130 Drive Cause:A DRIVE-CLiQ communications error has occurred. The nodes do not send and receive in synchronism. Various causes related to telegram timing and reception. Remedy: Check the power supply voltage of the component involved. Carry out a POWER ON (switch-off/switch-on). Replace theRead more ⟶
F40886 CX32 DRIVE-CLIQ (CU): Error when sending DRIVE-CLiQ data fault in Siemens SINAMICS G130 Drive
F40886 CX32 DRIVE-CLIQ (CU): Error when sending DRIVE-CLiQ data fault in Siemens SINAMICS G130 Drive Cause:A DRIVE-CLiQ communications error has occurred. Data were not able to be sent. Telegram type does not match send list. Remedy:Carry out a POWER ON (switch-off/switch-on).
F40887 CX32 DRIVE-CLiQ (CU): Component fault fault in Siemens SINAMICS G130 Drive
F40887 CX32 DRIVE-CLiQ (CU): Component fault fault in Siemens SINAMICS G130 Drive Cause:Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded. Various causes including telegram header/buffer errors and late responses. Remedy: Check the DRIVE-CLiQ wiring. Check the electrical cabinet design and cable routing for EMC compliance. If required, use another DRIVE-CLiQ socketRead more ⟶
F40895 CX32 DRIVE-CLIQ (CU): Cyclic data transfer error fault in Siemens SINAMICS G130 Drive
F40895 CX32 DRIVE-CLIQ (CU): Cyclic data transfer error fault in Siemens SINAMICS G130 Drive Cause:A DRIVE-CLiQ communications error has occurred. Synchronization error during alternating cyclic data transfer. Remedy:Carry out a POWER ON (switch-off/switch-on).