F7410 Current controller output limited Reaction: OFF2 Acknowledgement: IMMEDIATELY fault in Siemens SINAMICS V70 drive
Cause: The condition “I_act = 0 and Uq_set_1 longer than 16 ms at its limit” is present and can be caused by the following:
- Motor not connected or motor contactor open.
- No DC link voltage present.
- Motor Module defective.
Remedy:
- Connect the motor or check the motor contactor.
- Check the DC link voltage.
- Check the Motor Module.